EUR-Lex Access to European Union law

Back to EUR-Lex homepage

This document is an excerpt from the EUR-Lex website

Document 32024R1103R(01)

Corrigendum to Commission Regulation (EU) 2024/1103 of 18 April 2024 implementing Directive 2009/125/EC of the European Parliament and of the Council as regards ecodesign requirements for local space heaters and separate related controls and repealing Commission Regulation (EU) 2015/1188 (Official Journal of the European Union L, 2024/1103, 19 April 2024)

OJ L, 2024/90295, 17.5.2024, ELI: http://data.europa.eu/eli/reg/2024/1103/corrigendum/2024-05-17/oj (BG, ES, CS, DA, DE, ET, EL, EN, FR, GA, HR, IT, LV, LT, HU, MT, NL, PL, PT, RO, SK, SL, FI, SV)

ELI: http://data.europa.eu/eli/reg/2024/1103/corrigendum/2024-05-17/oj

European flag

Official Journal
of the European Union

EN

L series


2024/1103

17.5.2024

Corrigendum to Commission Regulation (EU) 2024/1103 of 18 April 2024 implementing Directive 2009/125/EC of the European Parliament and of the Council as regards ecodesign requirements for local space heaters and separate related controls and repealing Commission Regulation (EU) 2015/1188

( Official Journal of the European Union L, 2024/1103, 19 April 2024 )

On page 27, Annex III is replaced as follows:

‘ANNEX III

Measurement methods and calculations referred to in Article 3

For the purposes of compliance and verification of compliance with the requirements of this Regulation, measurements and calculations shall be made using harmonised standards the reference numbers of which have been published for this purpose in the Official Journal of the European Union, or using other reliable, accurate and reproducible methods that take into account the generally recognised state-of-the-art methods.

1.   GENERAL CONDITIONS FOR MEASUREMENTS AND CALCULATIONS

(1)

Declared values for seasonal space heating energy efficiency shall be rounded to the nearest one decimal place.

(2)

For electric local space heaters, declared values for nominal heat output shall be rounded to the nearest third decimal place. For all other local space heaters, declared values for nominal heat output shall be rounded to the nearest one decimal place.

(3)

Declared values for emissions shall be rounded to the nearest integer.

(4)

Where a parameter is declared pursuant to Article 4, its declared value shall be used by the manufacturer, importer or authorised representative for the calculations in this Annex.

(5)

For gas and liquid fuel local space heaters except commercial local space heaters, the flue gas temperature and the combustion air temperature shall be measured for the minimum total flue duct pipe length declared by the manufacturer in the installation manual but not more than 1,5 meters (sum of vertical and horizontal pipe length). If no declaration is available the measurement shall be performed with a total pipe length of 1,5 meters.

(6)

For separate related controls the correct functioning of the control functions shall be checked.

2.   GENERAL CONDITIONS FOR SEASONAL SPACE HEATING ENERGY EFFICIENCY

(1)

The seasonal space heating energy efficiency (ηS ) shall be calculated as the seasonal space heating energy efficiency in active mode (ηS,on ), corrected by contributions accounting for heat output control, auxiliary electricity consumption and permanent pilot flame energy consumption.

(2)

For local space heaters that are placed on the market together with the control, the seasonal space heating energy efficiency shall be measured and calculated with the control contained in the packaging.

(3)

For local space heaters placed on the market without control, the seasonal space heating energy efficiency shall be measured and calculated for each different combination of local space heater and control functions indicated by the manufacturer, importer or authorised representative according to Annex II, point 4(2)(a).

3.   GENERAL CONDITIONS FOR EMISSIONS

For gaseous and liquid fuel local space heaters the emissions of nitrogen oxides (NOx) shall be calculated as the sum of the measured nitrogen monoxide and nitrogen dioxide, and expressed in nitrogen dioxide. The measurement of nitrogen oxides emissions shall be concurrent with the measurement of the space heating energy efficiency.

For declaration and verification purposes the emission at full load NOx(max) applies.

4.   SPECIFIC CONDITIONS FOR SEASONAL SPACE HEATING ENERGY EFFICIENCY

(1)

The seasonal space heating energy efficiency of local space heaters is defined as:

(a)

for gaseous fuel local space heaters and liquid fuel local space heaters, except commercial local space heaters:

Formula

where

η S is the seasonal space heating energy efficiency, expressed in %;

ηs,on is the seasonal space heating energy efficiency in active mode, expressed in %;

(b)

for electric local space heaters

Formula

where:

η S is the seasonal space heating energy efficiency, expressed in %;

ηs,on is the seasonal space heating energy efficiency in active mode, expressed in %;

CC is the conversion coefficient;

(c)

for commercial local space heaters

Formula

where:

η S is the seasonal space heating energy efficiency, expressed in %;

ηs,on is the seasonal space heating energy efficiency in active mode, expressed in %;

F(1) is a correction factor accounting for a negative contribution to seasonal space heating efficiency due to adjusted contributions for options for the heat output, expressed in %;

F(4) is a correction factor accounting for a negative contribution to the seasonal space heating energy efficiency by auxiliary electricity consumption, expressed in %;

F(5) is a correction factor accounting for a negative contribution to the seasonal space heating energy efficiency by energy consumption of a permanent pilot flame, expressed in %;

(2)

the seasonal space heating energy efficiency in active mode

Formula

is calculated as:

(a)

for all local space heaters except commercial local space heaters:

Formula

where:

η th,nom is the useful efficiency at nominal heat output, expressed in %.

for electric local space heaters,

Formula

for gaseous fuel local space heaters and liquid fuel local space heaters, η th,nom is the useful efficiency at nominal heat output based on NCV;

F(2) is a correction factor accounting for a positive contribution to the seasonal space heating energy efficiency due to adjusted contributions of controls of indoor heating comfort, the values of which are mutually exclusive, cannot be added to each other;

F(3) is a correction factor accounting for a positive contribution to the seasonal space heating energy efficiency due to adjusted contributions of controls for indoor heating comfort, the values of which can be added to each other;

F(4) is a correction factor accounting for a negative contribution to the seasonal space heating energy efficiency by auxiliary electricity consumption;

F(5) is a correction factor accounting for a negative contribution to the seasonal space heating energy efficiency by energy consumption of a permanent pilot flame;

(b)

for commercial local space heaters:

Formula

where:

ηS,th is the weighted thermal efficiency, expressed in %;

ηS,RF is the emission efficiency, expressed in %;

(i)

the weighted thermal efficiency (ηS,th ) is calculated as follows:

for luminous local space heaters, ηS,th is 85,6%;

for tube local space heaters:

Formula

where:

ηth,nom is the thermal efficiency at nominal heat output, expressed in %, based on GCV;

ηth,min is the thermal efficiency at minimum heat output, expressed in %, based on GCV;

Fenv are the envelope losses of the heat generator, expressed in %;

if the heat generator of the tube local space heater is specified by the manufacturer to be installed in the indoor space to be heated, the envelope losses are 0 (zero);

if the heat generator of the tube local space heater is specified by the manufacturer to be installed outside the heated area, the envelope loss factor depends on the thermal transmittance of the envelope of the heat generator according to Table 8;

Table 8 : Envelope loss factor of the heat generator

Thermal transmittance of envelope (U)

Fenv

U ≤ 0,5

2,2 %

0,5 < U ≤ 1,0

2,4 %

1,0 < U ≤ 1,4

3,2 %

1,4 < U ≤ 2,0

3,6 %

U>2,0

6,0 %

(ii)

the emission efficiency (ηS,RF ) is calculated as follows:

Formula

where RFS is the radiant factor of the commercial local space heater, expressed in %;

for all commercial local space heaters except tube heater systems:

Formula

where:

RFnom , is the radiant factor at nominal heat output, expressed in %;

RFmin , is the radiant factor at minimum heat output, expressed in %;

for tube heater systems:

Formula

where:

RFnom,i , is the radiant factor per tube segment at nominal heat output, expressed in %;

RFmin,i , is the radiant factor per tube segment at minimum heat output, expressed in %;

Pheater,i , is the heat output per tube segment, expressed in kW, based on GCV;

Psystem , is the heat output of the complete tube system, expressed in kW, based on GCV;

the above equation only applies if the construction of the burner, tubes and reflectors of the tube segment as applied in the tube heater system is identical to a single tube local space heater and the settings that determine the performance of the tube segment are identical to those of a single tube local space heater;

(3)

the correction factor F(1) is calculated as follows:

Table 9: Correction factor F(1) for commercial local space heaters

If the heat output control type of the products is:

F(1) [%]

With the following limits

Single stage

Formula

 

Two stage

Formula

2,5% ≤ F(1) ≤ 5,0%

Modulating

Formula

0% ≤ F(1) ≤ 5,0%

(4)

the correction factor F(2), is equal to one of the factors according to Table 10, depending on which control function applies. Only one value can be selected; the functions mentioned in Table 10 shall be activated and functional when the equipment is placed on the market or put into service and activated with its initial setup after the equipment is reset to its factory default settings;

Table 10: Correction factor F(2)

If the product is placed on the market with (only one option may apply)

F(2)

for electric local space heaters

for gaseous and liquid fuel local space heaters

Portable

Fixed

Storage

Underfloor

Visibly glowing radiant

Towel rails

single stage heat output, no room temperature control

0

0

0

0

0

0

0

two or more manual stages, no temperature control

0,025

0

0

0

0,050

0,030

0,025

with mechanic thermostat room temperature control

0,100

0,025

0,025

0,025

0,025

0,030

0,050

with electronic room temperature control

0,160

0,050

0,050

0,050

0,080

0,030

0,100

with electronic room temperature control plus day timer

0,170

0,095

0,095

0,095

0,100

0,095

0,125

with electronic room temperature control plus week timer

0,190

0,150

0,150

0,150

0,120

0,150

0,150

(5)

the correction factor F(3) is calculated as the summation of the values according to Table 11, depending on which control function(s) applies; the functions mentioned in Table 11 shall be activated and functional when the equipment is placed on the market or put into service and activated with its initial setup after the equipment is reset to its factory default settings;

Table 11: Correction factor F(3)

If the product is placed on the market with (multiple options may apply):

F(3)

for electric local space heaters

for gaseous and liquid fuel local space heaters

Portable

Fixed

Storage

Underfloor

Visibly glowing radiant

Towel rails

room temperature control with presence detection

0, 005

0

0

0

0,040

0

0,025

room temperature control with open window detection

0,005

0,020

0,020

0,020

0,020

0,020

0,025

with distance control option

0

0,020

0,020

0,020

0

0

0,025

with adaptive start control

0,005

0,020

0,020

0,020

0

0,020

0

with working time limitation

0,005

0

0

0

0,020

0,020

0

with black bulb sensor

0

0

0

0

0,040

0

0

with self-learning functionality

0

0,020

0,020

0,020

0,010

0,020

0,0125

Control accuracy with CA < 2 Kelvin and CSD < 2 Kelvin

0,020

0,020

0,020

0,020

0

0,020

0,0125

(6)

the correction factor F(4) is calculated as:

(a)

for gaseous and liquid fuel local space heaters except commercial local space heaters:

Formula

where:

elmax is the electric power consumption at nominal heat output, expressed in kW;

elmin is the electric power consumption at minimum heat output, expressed in kW. In case the product does not offer a minimum heat output, the value for the electric power consumption at nominal heat output shall be used;

Pnom is the nominal heat output of the product, expressed in kW;

(b)

for commercial local space heaters:

Formula

(c)

for electric local space heaters F(4) = 1;

(7)

the correction factor F(5) is calculated as follows:

(a)

for gaseous or liquid fuel local space heaters except commercial local space heaters:

Formula

where:

Ppilot is the pilot flame consumption, expressed in kW;

Pnom is the nominal heat output of the product, expressed in kW;

(b)

for commercial local space heaters:

Formula

where:

Ppilot is the pilot flame consumption, expressed in kW;

Pnom is the nominal heat output of the product, expressed in kW;

in case the product has no permanent pilot light (flame) Ppilot is 0 (zero);

(c)

For electric local space heaters F(5) = 1.

5.   LOW POWER MODES

(1)

The power consumption of the off mode (Po ), standby mode (Psm ), and where applicable the idle mode (P idle ) and the networked standby mode (Pnsm ) are measured, expressed in W and rounded to two decimal places.

During measurements of the power consumption in low power modes, the following functions shall be checked and recorded:

(a)

the display or not of information;

(b)

the activation or not of a network connection.

If the standby mode includes the display of information or status, this function shall also be provided when the networked standby is provided.

(2)

For separate related controls, the power consumption of the low power modes shall be measured at the mains voltage. If the power consumption of the low power modes can only be measured at a DC voltage level, the results of these measurements for each low power mode shall be multiplied with a factor 1,5, representing an average AC-DC power conversion of 67%, to arrive at the values that shall comply with the requirements for low power modes.

6.   CONTROL ACCURACY AND CONTROL TO SETPOINT DEVIATION

For local space heaters and for separate related controls, CA and CSD shall be measured whenever the manufacturer declares a CA < 2K and a CSD < 2K.


ELI: http://data.europa.eu/eli/reg/2024/1103/corrigendum/2024-05-17/oj

ISSN 1977-0677 (electronic edition)


Top